7-10

Step 7 - Wire the Control Signal Terminal Block

1329I-5.5 Integrated Drive/Motor — January, 2000

7.7

Wiring Forward / Reverse Control

Important:

The terminal block forward/reverse functions are only active when in
terminal block start mode.

The Forward / Reverse input (the connection between terminals 13 and 14) defines the
requested direction of motor rotation. If the input is open, the requested direction is
forward. Switching the Forward / Reverse input causes the motor to ramp to rest and
then accelerate in the opposite direction. Note that the 1329I unit is shipped with the
forward direction defined as CCW shaft rotation as viewed from the motor shaft end.

Figure 7.13 shows the Forward / Reverse control wiring for the 1329I unit. If you disable
(lock out) reverse using the setup DIP switch, do not wire to this input because the drive
ignores any transition on this input. Refer to the setup DIP switch description in
Chapter 8

Figure 7.13
Forward / Reverse Control Wiring

7.8

Wiring Reset Control

An open-to-closed transition at the Reset input (control terminal 15) clears a fault once
the appropriate corrective action has been taken. After clearing the fault, you must
reassert the Start command in order to restart the unit.

Wire a normally-open (N.O.) push-button between control terminals 15 and 13 as shown
in Figure 7.14. Refer to Chapter 11, Diagnostics and Troubleshooting, for more
information on faults.

Figure 7.14
Reset Control Wiring

12
13
14
15

24 Volts DC

Forward/Reverse

Rev

Fwd

12
13
14
15
16

24 Volt DC

Reset