1 wire routing guidelines, Wire routing guidelines -3 – Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual
Page 17
Advertising
Step 2 - Plan the Installation
2-3
1329I-5.5 Integrated Drive/Motor — January, 2000
2.1
Wire Routing Guidelines
The 1329I unit is shipped from the factory with plastic conduit plugs installed. These
plugs must be removed. Before wiring, replace these plugs with appropriate 3/4-inch
NPT connectors having a similar enclosure rating. After wiring, seal unused routing
holes using permanent, user-supplied 3/4-inch NPT plugs. Seal all threaded
connections. Route the power and control wiring as shown in Figure 2.3.
Figure 2.3
Wire Entry Locations
PE
DC+
DC-
DBR
T/L3
S/L2
R/L1
Control Signal Wiring
AC Input Power Wiring
AC Input Power Wiring
Control Signal Wiring