Technical specifications, Appendix, Unit ratings – Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual

Page 65

Advertising
background image

1329I-5.5 Integrated Drive/Motor — January, 2000

Appendix

A

Technical Specifications

Unit Ratings

Input Ratings

AC line voltage:

• 380 to 460 VAC, 3-phase
• 200 to 230 VAC, 3-phase
• 200 to 230 VAC, 1-phase
• 115 VAC, 1-phase

AC line frequency:

• 48 to 62 Hz

AC line voltage variation:

• +/-10%

AC line current:

Max allowable AC line distribution KVA:

• 100 KVA maximum for 115 VAC to 460 VAC input.

Output Ratings

Horsepower ratings:

• 1, 2, 3 and 5 HP at 460 VAC
• 1, 2 HP at 230 VAC
• 1 HP at 115 VAC

Output voltage:

• 380 to 460 VAC, 3-phase
• 200 to 230 VAC, 3-phase
• 115 VAC, 3-phase

Input Voltage

Unit HP

Input Current

460 VAC

1 HP

2.3 A rms continuous

460 VAC

2 HP

3.7 A rms continuous

460 VAC

3 HP

5.7 A rms continuous

460 VAC

5 HP

9.0 A rms continuous

230 VAC

1 HP

4.5 A rms continuous

230 VAC

2 HP

7.6 A rms continuous

230 VAC, 1-phase

1 HP

5.8 A rms continuous

230 VAC, 1-phase

2 HP

14 A rms continuous

115 VAC

1 HP

14 A rms continuous

Advertising