Handling and Lifting Guidelines

Follow these handling and lifting guidelines:

• In the case of assemblies on a common base, carefully lift the assembly by a sling

around the base or by other lifting means on the base.

• When designing the lifting means, take care to assure lifting in the intended

direction.

• Do not lift the unit by the plastic blower cover.

• Do not use any lifting means under the Drive Section.

• Do not lift attached equipment by lifting the motor.

• Do not use the 1329I unit as a step.

2.3

CE Conformity

This drive is a component intended for implementation in machines or systems for the
industrial environment. It is CE marked for conformity to the Low Voltage (LV)
Directive 73/23/EEC when installed as described. It also has been tested to meet the
Council Directive 89/336 Electromagnetic Compatibility (EMC). The standards used
for this testing are, LV: EN50178, EN60204-1, EMC: EN61800-3, EN50081-1,
EN50082-2.

Important:

The conformity of the drive and filter to any standard does not guarantee
that the entire installation will conform. Many other factors can influence
the total installation and only direct measurements can verify total
conformity. It is therefore the responsibility of the machine manufacturer,
to ensure, that the conformity is met.

A copy of the Declaration of Conformity (DOC) is available from your local Rockwell
Automation Sales Office.

2.3.1 Essential Requirements for a Conforming EMC Installation

The following three items are required for CE Conformance:

1. A CE filter option (see Chapter 1) must be installed to reduce conducted

emissions.

2. Grounding of equipment and cable shields must be solid, with low impedance

connections.

3. All control and signal wiring must use shielded cable or be in grounded metal

conduit.