1329I-5.5 Integrated Drive/Motor — January, 2000

Chapter

7

Step 7 - Wire the Control Signal

Terminal Block

The following sections describe how to wire the control signal terminal block shown
in Figure 7.1.

Refer to either Figure 7.2 (standard units) or Figure 7.3 (local operator control units)
before you begin wiring. These figures show typical wiring connections and the sections
in this chapter where the signals are described in detail.

Note the following when wiring the terminal block:

• The terminal block is isolated from the input power.

• Route the control wires separately from the power wires.

• The terminal block accepts 0.326 mm

2

(22 AWG) through 3.31 mm

2

(12 AWG)

wire.

• The maximum lead length is 300 meters (1000 ft).

• The maximum tightening torque is 0.8 Nm (7 in-lb).