Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual

Page 32

Advertising
background image

7-4

Step 7 - Wire the Control Signal Terminal Block

1329I-5.5 Integrated Drive/Motor — January, 2000

Figure 7.3
Typical Control Signal Connections for Local Operator Control Units

Table 7.3
User Wiring for Local Operator Control Units

An external 0 to 10 volt DC or 4 to 20 mA speed reference source can be connected. See Section 7.5.3
for more information.

The jumper between terminals 7 and 11 must be removed when wiring the Function Loss input. See
Section 7.1 for more information.

The jumper between terminals 13 and 17 must be removed when wiring the Stop input. See Section
7.6 for more information.

Signal

Refer to Section

Function Loss

7.1

Analog Output

7.2

Relay Control Output

7.3

RPM/Percent Load Display

7.4

Speed Reference (select one)

Preset Speed

7.5.1

Speed Potentiometer

7.5.2

External Speed Reference (0 – 10V DC or 4 – 20 mA)

7.5.3

1
2

3
4
5
6
7
8
9
10
11
12
13

14
15
16
17
18
19
20

10 Volt Reference

0 – 10V DC Speed Reference Input

4 – 20 mA Speed Reference Input

Common

0 – 10 Volt Output

Common

Speed Preset 2

Speed Preset 1

Speed Preset 0

Forward/Reverse

24 Volt DC

RPM/Percent Load Display

Reset

Start

Stop

24 Volt DC Common

N.O. Relay

Relay Common

24 Volt DC

Function Loss

-

+

RPM

% Load