11-4

Diagnostics and Troubleshooting

1329I-5.5 Integrated Drive/Motor — January, 2000

Electronic Thermal Overload
The electronic thermal
overload will trip when the
current to the motor has
exceeded either 110%
(variable torque V/Hz curve
selected) or 150% (constant
torque V/Hz curve selected)
of the motor rated current for
60 seconds.

Excessive current to the motor
for an extended time due to
excessive load or short circuit.

Check for obstruction to shaft
rotation.
Reduce the driven load.
Verify input wiring is correctly
connected (see Section 5.0).
Check for blower obstruction.
Replace blower if required.

TB Redundant Start

Regulator board

malfunction

.

Remove power from unit. Check
the keypad cable connection.
Reapply power to the unit.

Internal Fault
(NNN = a number from 0 to
999)
The display flashes the fault
code on and off at 1/2
second intervals to indicate
an internal fault.

Control board

malfunction

.

Replace Control board.
Internal faults cannot be reset.

Code

Fault Description

Fault Cause

Corrective Action