Operating performance, Operating specifications, Mechanical specifications – Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual
Page 67
Technical Specifications
A-3
1329I-5.5 Integrated Drive/Motor — January, 2000
Operating Performance
Frequency regulation:
• 1% (1% of base speed, 180 to 1800 RPM, constant torque)
Speed range:
• 20:1 (90 to 1800 RPM, constant torque)
Voltage regulation:
• 3% of maximum rated voltage
Input power dip ride-through time:
• 500 msec minimum
Drive efficiency:
• >95% (at rated amps, 115-460 V, 60 Hz)
Operating Specifications
Operating temperature:
• 0 to 40˚C (32˚F to 104˚F) ambient
Storage temperature:
• -40˚C to 85˚C (-40˚F to 185˚F)
Altitude:
• 1000 meters (3300 feet maximum) without derating. For every 91.4 meters
(300 feet) above 1000 meters, derate the current by 1%. Above 3000 meters
(10,000 feet), consult your Allen-Bradley Sales Office
Humidity:
• 5% to 95%, non-condensing
Service factor:
• 1.0
Mechanical Specifications
Motor enclosure type:
• Totally enclosed, 24 VDC blower cooled (TEBC)
Required airflow:
• Required clearance for blower intake = 1 in
Protection rating:
• Drive Section is NEMA Type 12, motor is IEC IP54