8-2

Step 8 - Verify the Setup and Adjust Switches if Required

1329I-5.5 Integrated Drive/Motor — January, 2000

Figure 8.1
Rotary Switches and Setup DIP Switch Locations

8.1

Adjusting the Maximum Speed

The maximum speed rotary switch limits the speed reference to the unit. Regardless of
what speed reference is supplied, the unit will not command a speed greater than value
selected by this rotary switch.

Figure 8.2
Maximum Speed Rotary Switch Settings

Range: 1500 RPM (50 Hz) to 3600 RPM (120 Hz)

Default: 1800 RPM (60 Hz)

Max Speed Switch

(SW2)

Setup DIP Switch

(SW3)

Accel/Decel Switch

(SW1)

OFF

ON

PE

DC+

DC-

DBR

T/L3

S/L2

R/L1

ATTENTION: The user is responsible for ensuring that driven
machinery and all drive-train mechanisms are capable of safe operation
at maximum speed. Failure to observe this precaution could result in
severe bodily injury or loss of life.

0 = 1500 RPM (50 Hz)
1 = 1800 RPM (60 Hz) Default
2 = 2100 RPM (70 Hz)
3 = 2400 RPM (80 Hz)
4 = 2700 RPM (90 Hz)
5 = 3000 RPM (100 Hz)
6 = 3300 RPM (110 Hz)
7 = 3600 RPM (120 Hz)