Output state tab - output module, Ramp rate – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 107

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

107

Configure the Modules with RSLogix 5000 Software Chapter 7

Output State Tab -
Output Module

Use the following information to configure the parameters on the
Output State tab.

With an individual channel button selected, use this information to configure the
parameters in the Channel box that apply to the individual channels.

Ramp Rate

The ramping rate, which is set up on the Limits tab, limits the speed at which an
analog output signal can change. This prevents fast transitions in output from
damaging equipment that the output controls.

This feature is available in Hard Run mode.

Table 27 - Pass -through Setting, Ratio, and Priority

Setting

Scan:Pass-through ratio

Gives priority to

Once per channel scan

1:1

Asset management

Once per two channels scanned

1:2

Default setting

Once per module scan

1:8

Input tag scan