Unlatch alarms in the 1756-if8h module – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 150

Advertising
background image

150

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 10

Unlatch Alarms and Reconfigure Modules By Using Ladder Logic

Unlatch Alarms in the
1756-IF8H Module

The example ladder logic rungs 0…4 show how to unlatch the following alarms:

• Channel 0 High high alarm - Rung 0
• Channel 0 High alarm - Rung 1
• Channel 0 Low alarm - Rung 2
• Channel 0 Low low alarm - Rung 3
• Channel 0 Rate alarm - Rung 4

Rung 0 unlatches the high high alarm.

Rung 1 unlatches the high alarm.

Rung 2 unlatches the low alarm.

Rung 3 unlatches the low low alarm.

Rung 4 unlatches the rate alarm.

Click the box in
each rung to see
the configuration
and communication
information dialog
associated with it.

IMPORTANT

An I/O module must be configured to latch alarms, before you
can perform unlatch services using ladder logic. If an unlatch
service is received by a module not configured to latch alarms,
the message instruction errors.

All alarms for channel 0 can be unlatched simultaneously with
a single message instruction by leaving the Attribute
box blank.