Exact match – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 1 ControlLogix HART Analog I/O Modules

You can find revision information on the General tab of a module’s Properties
dialog box.

Figure 1 - General Tab

Exact Match

Exact Match keying requires all keying attributes, that is, Vendor, Product Type,
Product Code (catalog number), Major Revision, and Minor Revision, of the
physical module and the module created in the software to match precisely to
establish communication. If any attribute does not match precisely, I/O
communication is not permitted with the module or with modules connected
through it, as in the case of a communication module.

Use Exact Match keying when you need the system to verify that the module
revisions in use are exactly as specified in the project, such as for use in highly-
regulated industries. Exact Match keying is also necessary to enable Automatic
Firmware Update for the module via the Firmware Supervisor feature from a
Logix5000 controller.

IMPORTANT

Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may
result in a loss of data.

Advertising