1756-if8h fault reporting – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 64

Advertising
background image

64

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 4

1756-IF8H HART Analog Input Module

1756-IF8H Fault Reporting

The graphic below offers an overview of the fault reporting process for the
1756-IF8H module.

If set, any bit in the Channel Fault word also sets the
Analog Group Fault in the Module Fault word.

A channel calibration fault
sets the calibration fault in
the Module Fault word.

An underrange, overrange condition
sets appropriate Channel Fault bits.

When the module is calibrating, all
bits in the Channel Fault word are set.

Alarm bits 0…4 in the Channel Status word do not set additional
bits at any higher level. You must monitor these conditions here.

41514

Module Faults

Channel Faults

Channel Status Tags

7

Analog

GroupFault

6

2

Calibrating

1

CalFault

6, 5, 4, and 0 are not used for fault reporting

7

Ch7Fault

6

Ch6Fault

5

Ch5Fault

4

Ch4Fault

3

Ch3Fault

2

Ch2Fault

1

Ch1Fault

0

Ch0Fault

7

CalFault

6

Underrange

5

Overrange

4

RateAlarm

3

LAlarm

2

HAlarm

1

LLAlarm

0

HHAlarm

Ch0

Ch1

Ch2

Ch3

Ch4

Ch5

Ch6

Ch7

0

One set of tags for each channel

3

Updated

StatusReady

Advertising