Module-defined data types, 1756-if16h module, Configuration – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 173

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

173

Tag Definitions Appendix A

Module-defined Data
Types, 1756-IF16H Module

These tables describe module-defined data types for the 1756-IF16H module
and include information for configuration and input tags.

Configuration

This table describes the configuration tags available in the 1756-IF16H module.

Table 62 - Configuration (AB:1756_IF16H:C:0)

Member Name

Type

Style

Description

ModuleFilter
(bits 0…7)

SINT

Decimal

See the

Module Filter Values table on page 103

.

RealTimeSample
(bits 0…15)

INT

Decimal

Milliseconds between reading signal values. See

Real Time Sample (RTS) on page 41

for more

information.

Ch00Config AB:1756_IF16H_ChConfig_Struct:C:0

Config

SINT

Binary

HARTEn

BOOL

Decimal

Ch00Config.Config.7, Enable HART communication. Must be 1 for valid HART data in input tag and
asset management access to HART field device.

RangeType

SINT

Decimal

0 = 0…20 mA
1 = 4 …20 mA

DigitalFilter

INT

Decimal

Time constant of low pass filter in ms. See

Digital Filter on page 71

for more information.

LowSignal

REAL

Float

Lower current value for scaling to engineering units. Default is 4 mA. Must be less than HighSignal
and more than or equal to the minimum input range. See

Scaling to Engineering Units on page 98

for

more information.

HighSignal

REAL

Float

Upper current value for scaling to engineering units. Default is 20 mA. Must be more than LowSignal
and less than or equal to the maximum input Range. See

Scaling to Engineering Units on page 98

for

more information.

LowEngineering

REAL

Float

Measured quantity in engineering units that results in a signal level equal to LowSignal. See

Scaling

to Engineering Units on page 98

for more information.

HighEngineering

REAL

Float

Measured quantity in engineering units that results in a signal level equal to HighSignal. See

Scaling

to Engineering Units on page 98

for more information.

CalBias

REAL

Float

Sensor Offset in engineering units added to the measured signal before reporting Ch00.Data.

Ch01Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch02Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch03Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch04Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch05Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch06Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch07Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch08Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch09Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch10Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch11Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch12Config

AB:1756_IF16H_ChConfig_Struct:C:0

Ch13Config

AB:1756_IF16H_ChConfig_Struct:C:0