Tag Definitions Appendix A

ConfigurationChanged

BOOL

Decimal

The field device configuration has changed and new field device configuration information can be
obtained from the 1756-IF16H module via CIP MSG GetDeviceInfo, which will clear this bit.

MaintenanceRequired

BOOL

Bit 0 of Extended Device Status (if using CMD 9, or from CMD 48 if supported).

BrokenWire

BOOL

Decimal

Indicates that current is not flowing through the module as expected. This might be caused by
broken wiring, RTB removal, or a powered-off field device.

HARTFault

BOOL

Decimal

Indicates a problem with HART data from the field device on Channel x.
Examples are HART not enabled, HART device not connected, HART communication failure
due to noise.
The following Field Device Status conditions also cause this to be set: Device Malfunction,
PV Out of Limits, Loop Current Saturated, and Loop Current Fixed.

ResponseCode

SINT

Binary

HART communication status byte or Response code from a recent HART reply. See

Response Code

and Field Device Status on page 195

for more information.

FieldDeviceStatus

SINT

Binary

HART device status byte from a recent HART reply. Indicates the health of the HART Field device.
See

Field Device Status Bit Mask Definitions on page 196

for more information.

AlarmStatus

SINT

Binary

Indicates various alarms on the analog signal.

DeviceVariableAlert

BOOL

AlarmStatus.4, Bit 1 of Extended Device Status. Device reports a problem with some measurement.

Overrange

BOOL

AlarmStatus.5, Signal value over range (over 20 MA).

Underrange

BOOL

AlarmStatus.6, Signal value under range.
(less than 3.4 mA if configured for 4…20 mA).

CalFault

BOOL

AlarmStatus.7, Bad calibration.

PV

REAL

Float

Primary value. This is the same value as signaled on the analog channel and is the most important
measurement made by this device.

SV

REAL

Float

Secondary value

TV

REAL

Float

Third value

FV

REAL

Float

Fourth value

PVStatus

SINT

Hex

Primary status
16#C0 = Connected
16#00 = Not Connected

SVStatus

SINT

Hex

Secondary status
16#C0 = Connected
16#00 = Not Connected

TVStatus

SINT

Hex

Third status
16#C0 = Connected
16#00 = Not Connected

FVStatus

SINT

Hex

Fourth status
16#C0 = Connected
16#00 = Not Connected

Ch01

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 01 analog and HART data.

Ch02

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 02 analog and HART data.

Ch03

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 03 analog and HART data.

Ch04

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 04 analog and HART data.

Ch05

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 05 analog and HART data.

Ch06

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 06 analog and HART data.

Ch07

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 07 analog and HART data.

Ch08

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 08 analog and HART data.

Ch09

AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 09 analog and HART data.

Table 65 - Analog and HART by Channel (AB:1756-IF16H_AnalogHARTbyChannel:I:0)

Member Name

Type

Style

Description