Module troubleshooting, Use module indicators, Chapter 11 – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 155: Introduction use module indicators, Chapter, Introduction

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

155

Chapter

11

Module Troubleshooting

Introduction

This chapter describes how to interpret status indicators and troubleshoot
the modules.

These topics are discussed in this chapter.

Use Module Indicators

The analog I/O modules have indicators that provide indication of module
status. ControlLogix modules use status indicators as shown in the table.

The illustration below shows the status indicators used with ControlLogix analog
input HART modules.

The following tables provide a description of the colors that display in the
status indicators.

Topic

Page

Use Module Indicators

155

General Troubleshooting Tips

156

Use RSLogix 5000 Software to Troubleshoot a Module

159

Module Configuration Errors

160

ANALOG INPUT

CAL

OK

20962-M

Table 49 - ControlLogix Module Status Indicators

Indicator

Display

Means

Recommended Action

OK

Steady Green

The inputs are being multicast

None

OK

Flashing Green

The module has passed internal diagnostics, but is not currently performing connected
communication

None

OK

Flashing Red

Previously established communication has timed out

Check controller

OK

Steady Red

It is likely the module should be replaced

See the blink codes

(1)

CAL

Flashing Green

The module is in Calibration mode

None

(1) Under fault conditions the module communicates a particular error via the status indicator blink codes.

Table 50

provides a description of the fault

conditions and blink codes.