Appendix A Tag Definitions

Module-defined Data
Types, 1756-IF8H Module

These tables describe module-defined data types for the 1756-IF8H module and
include information for configuration and input tags.

Configuration

This table describes the configuration tags available in the 1756-IF8H module.

Analog and HART PV

Configuration

AB:1756_OF8H:C:0

AB:1756_OF8H_ChConfig_Struct:C:0

Input

AB:1756_OF8H_HARTPV:I:1

AB:1756_OF8H_HARTData:I:1
AB:1756_OF8H_HARTStatus_Struct:I:1

Output

AB:1756_OF8H:O:0

None

Analog and HART by
Channel

Configuration

AB:1756_OF8H:C:0

AB:1756_OF8H_ChConfig_Struct:C:0

Input

AB:1756_OF8H_AnalogHARTbyChannel:I:0

AB:1756_OF8H_HARTDataAll_Struct:I:0
AB:1756_OF8H_HARTStatusAll_Struct:I:0

Output

AB:1756_OF8H:O:0

None

Table 57 - 1756-OF8H Input Data Choice and Tags

Input Data Choice

Tag

Main Module Defined Type

Subtype Used by Main Type

Table 58 - Configuration (AB:1756_IF8H:C:0)

Member Name

Type

Style

Description

ModuleFilter
(bits 0…7)

SINT

Decimal

See the

Module Filter Values table on page 103

.

RealTimeSample
(bits 0…15)

INT

Decimal

Milliseconds between reading signal values. See

Real Time Sample (RTS) on page 41

for more

information.

Ch0Config AB:1756_IF8H_ChConfig_Struct:C:0

Config

SINT

Binary

RateAlarmLatch

BOOL

Decimal

Ch0Config.Config.4, After a Rate Alarm is detected, keep I.ChxRateAlarm set even after Rate returns
to normal, until unlatched by CIP Service Message.

ProcessAlarmLatch

BOOL

Decimal

Ch0Config.Config.5, After a Process Alarm such as LL is detected, keep I.ChxLLAlarm set even after
measurement returns to normal, until unlatched by CIP Service Message.

AlarmDisable

BOOL

Decimal

Ch0Config.Config.6, Do not report Process or Rate Alarms.

HARTEn

BOOL

Decimal

Ch0Config.Config.7, Enable HART communication. Must be 1 for valid HART data in Input Tag and
Asset Management access to HART Field Device.

RangeType

SINT

Decimal

0 = -10…+10 V.
1 = 0…5 V.
2 = 0…10 V.
3 = 0…20 mA.
4 = 4 …20 mA.

DigitalFilter

INT

Decimal

Time Constant of low pass filter in ms. See

Digital Filter on page 71

for more information.

RateAlarmLimit

REAL

Float

Maximum Ramp Rate value to trigger a Rate Alarm when the Input Signal rate of change exceeds the
setpoint. See

Scaling to Engineering Units on page 98

for more information.

LowSignal

REAL

Float

Lower current value for scaling to engineering units. Default is 4 mA. Must be less than HighSignal
and more than or equal to the minimum Input Range. See

Scaling to Engineering Units on page 98

for

more information.