Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 127

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

127

Getting HART Data By Using CIP MSG Chapter 8

56…91

Message

HARTMsg

CMD#12, Bytes 0…23
See

HARTMsg on page 130

for more information.

92

PVCode

SINT

CMD#50, Bytes 0, 16#ff if not supported

93

SVCode

CMD#50, Bytes 1, 16#ff if not supported

94

TVCode

CMD#50, Bytes 2, 16#ff if not supported

95

FVCode

CMD#50, Bytes 3, 16#ff if not supported

96

PVUnits

CMD#3, Byte 4

97

SVUnits

CMD#3, Byte 9, 0 if not present

98

TVUnits

CMD#3, Byte 14, 0 if not present

99

FVUnits

CMD#3, Byte 19, 0 if not present

100

TransferFunction

CMD#15, Byte 1

101

RangeUnits

CMD#15, Byte 2

102…103

Expanded Device
Type Code

CMD#0, Byte 2 if HART revision is < 7
CMD#0, Bytes 1…2 if HART revision is

≥ 7

104…107

PVLowerRange

REAL

CMD#15, Bytes 3…6

108…111

PVUpperRange

CMD#15, Bytes 7…10

112…115

DampingValue

CMD#15, Bytes 11…14

116

WriteProtectCode

SINT

CMD#15, Byte 15

117

Pad_8 for 32 bit
alignment

118…119

Private Label
Manufacturer 16 bit

CMD#0, Byte 2 if HART revision is < 7
CMD#0, Bytes 19…20 if HART revision is

≥ 7

Reply Size = 120 bytes

(1) See

Appendix C on page 193

for related information.

Table 39 - Reply Packet - Request Succeeded

Offset

Field

Data Type

Definition

(1)