1756-if16h fault reporting – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 76

Advertising
background image

76

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 5

1756-IF16H HART Analog Input Module

1756-IF16H Fault Reporting

This graphic offers an overview of the fault reporting process for the
1756-IF16H module.

If set, any bit in the Channel Fault word also sets the
Analog Group Fault in the Module Fault word.

A channel
calibration fault
sets the calibration
fault in the Module
Fault word.

An underrange, overrange condition
sets appropriate Channel Fault bits.

When the module is
calibrating, all bits in the
Channel Fault word are set.

0…4 are not used

41514

One set of tags for each channel

Module Faults

Channel Faults

Channel Status Tags

7

Analog

GroupFault

1

0

0…5 are not used

15

Ch15Fault

14

Ch14Fault

13

Ch13Fault

12

Ch12Fault

2

Ch02Fault

1

Ch01Fault

0

Ch00Fault

7

CalFault or

Device.

CalFault

6

Underrange

5

Overrange

4

3

2

1

0

Ch00

Ch01

Ch02

Ch12

Ch13

Ch14

Ch15

6

CalFault

Module Status

7

0

Calibrating

6

1

Updated

StatusReady

Advertising