1756-if16h module fault and status reporting – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

75

1756-IF16H HART Analog Input Module Chapter 5

1756-IF16H Module Fault
and Status Reporting

The 1756-IF16H module sends status/fault data to the controller with its
channel data. The fault data is arranged to let you choose the level of granularity
you desire for examining fault conditions. Three levels of tags work together to
provide an increasing degree of detail as to the specific cause of faults on the
module.

Table 12

shows the tags that can be examined in ladder logic to indicate when a

fault has occurred.

Table 12 - Tags That Can Be Examined in Ladder Logic

Tag

Description

Tag Name
Analog and HART PV

Tag Name
Analog and HART by Channel

Module Fault Word

This word provides fault summary reporting.

ModuleFaults

ModuleFaults

Channel Fault Word

This word provides clamp and communication
fault reporting.

ChannelFaults
ChxxFault

ChannelFaults
ChxxFault

Channel Status Tags

These words provide individual channel limit, hold,
open wire, ramp status, and calibration faults.

ChxxStatus

Chxx.Device Status
Chxx.DeviceStatus.AlarmStatus

HART Faults

This provides HART communication status.

HARTFaults,
ChxxHARTFault

Chxx.DeviceStatus.HARTFault

HART Device Status

This provides HART field device health.

HART.ChxxDevice Status

Chxx.DeviceStatus.FieldDeviceStatus