Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

125

Getting HART Data By Using CIP MSG Chapter 8

Read Additional Status (Service Code = 16#4C)

These tables show the request and reply packet structures for the Read Additional
Status service. Reply Size = 2…224 bytes.

Table 34 - Request Packet

Offset

Field

Data Type

Definition

No request data

Request size = 0 bytes

Table 35 - Reply Packet - Request Failed

Offset

Field

Data Type

Definition

0

Status

USINT

Command status

1

Pad

Pad byte

Reply size = 2 bytes

Request Failed

Table 36 - Reply Packet - Request Succeeded

Offset

Offset

Data Type

Definition

0

Status

USINT

Command status

1

Count

Number of Ext Status bytes available

2

26

Ext Status Bytes

Extended Status bytes returned by CMD48

7

Pad

Pad type

Reply Size = Instance 1…8: 2…28 bytes; Instance 0: 224 bytes. If sent to Instance 0, all channels of the module will be included in the response, resulting
in 28 bytes per channel (27 bytes of response to the HART Read Additional Status plus 1 byte of pad to align the data to a 32 bit boundary.)