North american hazardous location approval – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 27

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

27

Module Installation Chapter 2

North American Hazardous
Location Approval

WARNING:

This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined by
Rockwell Automation.

Provision shall be made to prevent the rated voltage from being exceeded
by transient disturbances of more than 40% when applied in Zone 2
environments.

This equipment must be used only with ATEX certified Rockwell
Automation backplanes.

Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided
with this product.

Do not disconnect equipment unless power has been removed or the area
is known to be nonhazardous.

The following information applies when operating this
equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en
environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à
une utilisation en environnements de Classe I Division 2 Groupes A, B,
C, D dangereux et non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de température le
plus défavorable (code de température le plus faible) peut être utilisé
pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de
l'installation.

EXPLOSION HAZARD

Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.

Do not disconnect connections to this
equipment unless power has been removed or
the area is known to be nonhazardous. Secure
any external connections that mate to this
equipment by using screws, sliding latches,
threaded connectors, or other means provided
with this product.

Substitution of components may impair
suitability for Class I, Division 2.

If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.

RISQUE D’EXPLOSION

Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher l'équipement.

Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à
l'aide de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce produit.

La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.

S'assurer que l'environnement est classé non
dangereux avant de changer les piles.