Chapter 8

Getting HART Data By Using CIP MSG

If your input tag includes the HART PV data, a status indicator
HART.ChxDeviceStatus.MsgReady tells your program a HART reply is ready to
retrieve with the Pass-through Query command.

The CIP reply from the Init service includes a number called the handle. This
handle identifies the HART message that was placed in a queue for transmission
to the field device. When the reply is received and MsgReady is set to 1, your
Logix controller should send a Query containing that same handle to retrieve the
HART reply. The reason these steps are necessary is that it can take a long time
for the HART command to be transmitted and a reply received. If all eight
channels are in use, the time for a reply would be about 10 seconds if there was no
other pass-through traffic.