Limit example – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 110

Advertising
background image

110

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 7

Configure the Modules with RSLogix 5000 Software

Limit Example

If your output controls a valve positioner that is configured to use Percent of
Stroke for engineering units, and you don't want the valve to be over 62% open at
any time for any reason, then you can enter 0 as the Low Clamp and 62 for High
Clamp. Even if a PIDE instruction calculates the valve should be open more to
achieve process Setpoint, the output module clamps it to 62% open.

Ramp in Run Mode

Check

Enables ramping in Run mode.
Ramping occurs between the current output level and any new output

value received.

If ramping is enabled, the output only can change at the configured ramp

rate limit.

No

Ramp Rate

Enter a value from
9,999,9999 to
999,999,999,
default is 0.

Defines the maximum rate of change an output can make in engineering

units/second.

Serves as a trigger point for a Ramp Rate Limit alarm when the Ramp in

Run mode is selected.

Can also be uses to ramp a user-defined value in Program or Fault mode.
A non-editable copy of Ramp Rate is shown on the Output State tab.

No

Unlatch All

Click

Unlatches all alarms.
Is not available when the project is offline.

Yes

Unlatch

Click

Unlatches the adjacent alarm condition.
Is not available when the project is offline.

Yes

Disable All Alarms

Check

Disables all alarms for a channel.

No

Latch Limit Alarms

Check

Maintains the high and low limit alarms even after the condition ceases. The
high and low limit alarm is set if the requested output is beyond the clamp
limit (>High or <Low). This is useful if you want to detect a transient alarm
condition and preserve its indication until the alarm is explicitly unlatched.
Click Unlatch to unlatch an alarm, or send a Common Industrial Protocol (

CIP

)

message using the MSG instruction.

No

Latch Rate Alarm

Check

When enabled, a Rate Alarm indication remains set, even when the alarm
condition returns to normal. This latch lets you maintain the alarm even after
the condition ceases. The alarm unlatches only with an explicit message
acknowledging the alarm.

No

Table 28 - Alarm Tab Parameters (Continued)

Parameter

Action

Notes

Available in
Hard Run
Mode?

Advertising