Module filter – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

55

1756-IF8H HART Analog Input Module Chapter 4

Module Filter

The module filter attenuates the input signal beginning at the specified
frequency. This feature is applied on a module-wide basis, affecting all channels.

The module attenuates the selected frequency by approximately -3 dB or 0.707 of
the applied amplitude. An input signal with frequencies above the selected
frequency is attenuated more while frequencies below the selection receive
no attenuation.

In addition to frequency rejection, a by-product of the filter selection is the
minimum sample rate (RTS) that is available. For example, the 1000 Hz selection
does not attenuate any frequencies less than 1000 Hz, and provides for sampling
of all 16 channels within 18 ms. The 10 Hz selection attenuates all frequencies
above 10 Hz and provides only for sampling all 16 channels within 488 ms.

Use the following table to choose a module filter setting.

IMPORTANT

60 Hz is the default setting for the module filter. Do not use the 1000 Hz
module filter with HART instruments.

.707

60 Hz

0

Table 2 - Module Filter Selections with Associated Performance Data

Module Filter Setting (-3 dB)

(1)

10 Hz

15 Hz

20 Hz

50 Hz

60 Hz

100 Hz

250 Hz

1000 Hz

Minimum Sample Time (ms) (RTS)

488

328

248

88

88

56

28

18

Effective Resolution (+/-10V range)

17 bits

17 bits

17 bits

16 bits

16 bits

15 bits

14 bits

12 bits

0.16 mV

0.16 mV

0.16 mV

0.31 mV

0.31 mV

0.62 mV

1.25 mV

5.0 mV

Effective Resolution (0…10V range)

16 bits

16 bits

16 bits

15 bits

15 bits

14 bits

13 bits

11 bits

0.16 mV

0.16 mV

0.16 mV

0.31 mV

0.31 mV

0.62 mV

1.25 mV

5.0 mV

Effective Resolution (0…5V, 0 …20 mA,
4…20 mA range)

15 bits

15 bits

15 bits

14 bits

14 bits

13 bits

12 bits

10 bits

0.16 mV
0.63

μA

0.16 mV
0.63

μA

0.16 mV
0.63

μA

0.31 mV
1.25

μA

0.31 mV
1.25

μA

0.62 mV
2.5

μA

1.25 mV
5.0

μA

5.0 mV
20.0

μA

-3 dB Frequency

7.80 Hz

11.70 Hz

15.60 Hz

39.30 Hz

39.30 Hz

65.54 Hz

163.9 Hz

659.7 Hz

50 Hz Rejection

95 dB

85 dB

38 dB

4 dB

4 dB

2 dB

0.5 dB

0.1 dB

60 Hz Rejection

97 dB

88 dB

65 dB

7 dB

7 dB

2.5 dB

0.6 dB

0.1 dB

(1) Worst case settling time to 100% of a step change is double the real time sample time.

Advertising