Power requirements – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 29

Advertising
background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

29

Module Installation Chapter 2

Power Requirements

These modules receive power from the 1756 chassis power supply and require
these two sources of power from the backplane.

ATTENTION: To comply with the CE low voltage directive (LVD), all
connected I/O must be powered from a source compliant with safety extra
low voltage (SELV) or protected extra low voltage (PELV).

WARNING: Use supply wires suitable for 30 °C (86 °F) above
surrounding ambient.

Module

Power Requirements, max

1756-IF8H

300 mA at 5.1V DC
135 mA at 24V DC

1756-IF16H

200 mA at 5.1V DC
125 mA at 24V DC

1756-OF8H

200 mA at 5.1 V DC
230 mA at 24 V DC

IMPORTANT

The 1756-OF8H module requires more power than the standard 1756-OF8
module. You can have a maximum of 12 1756-OF8H modules per chassis.

ATTENTION: Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in using
the system.

Advertising