Module configuration errors, Additional fault codes - module level – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 160

Advertising
background image

160

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 11

Module Troubleshooting

Module Configuration
Errors

The additional fault code value describes the configuration error if
“(Code 16#0009) Module Configuration Rejected: Parameter Error” is
displayed on the Connection Tab in RSLogix 5000 software.

Additional Fault Codes - Module Level

Table 51

shows error codes used by ControlLogix HART Analog modules for

module level conditions (conditions that do not occur in a specific channel).

Table 51 - 1756-IF8H, 1756-IF16H, and 1756-OF8H Module Level Error Codes

Additional Fault Codes

Description

16#0001

Configuration revision number invalid
Valid numbers are 0 or 1

16#0002

Filter value invalid

16#0003

RTS invalid

16#0004

Pass-through handle timeout

16#1001

Configuration does not match
In a multiple owner setup, with the configuration revision
number set to 1, the configurations must match

TIP

The 16# means this number is Hex display style.