Publication 1734-UM015A-EN-E - November 2009

106 Peer Data Maps

See the

Very High Speed Counter Input Modules

section for an example of

how to convert Word Data to Double Word in your DeviceLogix program.

RS232 and RS485 Interface Module

1734-232ASC, 1734-485ASC, 1738-232ASCM12, 1738-485ASCM12

Although the RS232 and RS485 modules can produce up to 132 bytes of data,
only a message of 24 bytes can be consumed by the DeviceLogix module.

The data from these modules can be addressed in the DeviceLogix program
using either bit or word tags.

Peer X (byte 0, bit 0)…Peer X (byte 23, bit 7)

Peer X (word 0)…Peer X (word 11)

Peer X (byte 8, bit 2)

DEC - SSI data count decreasing

Peer X (byte 8, bit 3)

INC - SSI data count increasing

Peer X (byte 8, bit 4)

C1R - Comparator 1 value reached

Peer X (byte 8, bit 5)

C2R - Comparator 2 value reached

Peer X (byte 8, bit 6)

C1ST - Comparator 1 active

Peer X (byte 8, bit 7)

C2ST - Comparator 2 active

Peer X (byte 9, bit 0)

SPF - SSI sensor power fault

Peer X (byte 9, bit 1)

CCF - Coprocessor configuration fault

Peer X (byte 9, bit 2)

CCE - Coprocessor communication error

Peer X (byte 9, bit 3)

IDF - SSI input data fault

Peer X (byte 9, bit 4)

LHON - Latched data is stored

Input Tags for Synchronous Serial Interface Modules (Continued)

Input Tag in DeviceLogix Editor

Data