Chapter

2

Install POINT I/O DeviceLogix Modules

If you are using ArmorPOINT I/O modules
(1738-8CFGDLXM8/M12/M23), go to

Chapter 3, Install ArmorPOINT I/O

DeviceLogix Modules

.

About This Chapter

Read this chapter for installation and wiring information including how to
complete the following:

Install the Mounting Base Assembly

Install an I/O Module

Install the Removable Terminal Block

Remove a 1734-TB or 1734-TBS Base

Wire the Modules

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications
(as defined in IEC publication 60664-1), at altitudes up to 2000 m
(6561 ft) without derating.

This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.

This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from
accessibility to live parts. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain
product safety certifications.

See NEMA Standards 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by different
types of enclosure. Also, see the appropriate sections in this
publication, as well as the Allen-Bradley publication 1770-4.1
(Industrial Automation Wiring and Grounding Guidelines), for
additional installation requirements pertaining to this equipment.