70 DeviceLogix Capabilities

For more information on the Move/Logical category, refer to the
DeviceLogix System User Manual, publication

RA-UM003

.

Logic Execution Time

The execution time is dependent on the total number of function blocks used
in the entire DeviceLogix program.

The module will execute the entire logic program before applying the outputs.
The module follows these steps:

1. Sample all inputs (hardware, network, peer).

2. Execute logic.

3. Apply all outputs (hardware, network).

RS (Reset Dominant)

0

0

0

0

0

1

0

1

1

0

0

0

1

1

0

0

0

0

1

1

0

1

1

1

1

0

1

0

1

1

1

0

Number of Function Blocks

Expected Execution Time (ms)

0…40

1

41…100

2

101…144

3

Function Block Type

Reset

Set

Value at time +
t

0

Value at time +
t

0+1