Publication 1734-UM015A-EN-E - November 2009

42 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet

Configuration of the modules must be done through RSNetWorx for
DeviceNet. See

Chapter 6

for details.

Data [34]

Peer 4 - EPS (ms)

Data [35]

Data [36]

Peer 5 - Slot/MacID

Data [37]

Peer 5 - Consume Message Length (bytes)

Data [38]

Peer 5 - EPR (ms)

Data [39]

Data [40]

Peer 6 - Slot/MacID

Data [41]

Peer 6 - Consume Message Length (bytes)

Data [42]

Peer 6 - EPR (ms)

Data [43]

Data [44]

Peer 7 - Slot/MacID

Data [45]

Peer 7 - Consume Message Length (bytes)

Data [46]

Peer 7 - EPR (ms)

Data [47]

Where:

Filter = 0 to 65535

μ

s (1000 = default)

FltM = Fault Mode (0 = Use Fault Value (default), 1 = Hold Last State)

FltV = Fault Value (0 = OFF (default), 1 = ON)

IdlM = Idle Mode (0 = Use Idle Value (default), 1 = Hold Last State)

IdlV = Idle Value (0 = OFF (default), 1 = ON)

RACK = Produce with Rack Assembly 4 and Consume Rack Assembly 34
(0 = Disabled (default), 1 = Enabled)

CFO = DeviceLogix Communication Fault Override of Outputs
1 = Enabled. When enabled, the DeviceLogix program will continue to control the
outputs even in the event of a communication fault.
0 = Disabled (default). When disabled, the outputs will follow the Fault and Idle
settings in the event of a communication fault.

DM = Dependent Mode
1 = Enabled. When enabled, the DeviceLogix program execution will follow the
Run/Idle state of the owning processor.

MP = Masterless Produce
0 = Disabled (default), 1 = Enabled. When enabled, the module will begin producing
data at powerup and after a connection with a controller is terminated.

EPR = Expected Packet Rate

PIT = Production Inhibit Time

Slot/MacID = Address of peer

Data Map - Configuration Assembly Instance 123 (Continued)

Message Size: 48 Bytes