Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 42

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

40 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet

You can select other produced assemblies:

Produced assembly instance 4 is the first byte of produced assembly
instance 101 (Data [0]).

Produced assembly instance 111 is the first eight bytes of produced
assembly instance 101 (Data [0]…[7]).

You can select other consumed assemblies:

Consumed assembly instance 34 is the first byte of consumed assembly
instance 102 (Data [0]).

Consumed assembly instance 112 is the first eight bytes of consumed
assembly instance 102 (Data [0]…[7]).

Default Data Map - Consumed Assembly Instance 102

Message Size: 20 Bytes

Bit

7

6

5

4

3

2

1

0

Data [0]

Pt 07

Pt 06

Pt 05

Pt 04

Pt 03

Pt 02

Pt 01

Pt 00

Data [1]

CNB 07 CNB 06 CNB 05 CNB 04 CNB 03 CNB 02 CNB 01 CNB 00

Data [2]

Reserved

Data [3]

Data [4]

Consumed Network Analog Word 0

Data [5]

Data [6]

Consumed Network Analog Word 1

Data [7]

Data [8]

Consumed Network Analog Word 2

Data [9]

Data [10]

Consumed Network Analog Word 3

Data [11]

Data [12]

Consumed Network Analog Word 4

Data [13]

Data [14]

Consumed Network Analog Word 5

Data [15]

Data [16]

Consumed Network Analog Word 6

Data [17]

Data [18]

Consumed Network Analog Word 7

Data [19]

Where: Pt = value to be applied to the output point, CNB = Consumed Network Bit

Advertising