Publication 1734-UM015A-EN-E - November 2009

Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetworx for DeviceNet 55

Consume data from a safety connection
The module can consume data from a safety module with a standard
connection.

Consume data sent to a peer from a master.

Set Up Peer Communication Parameters

For each peer, you need to configure a set of parameters.

Here are the three parameters in their default settings (no peer data).

Example

To listen to the data from a 1734-IB4 module in the first slot (node 1), you can
configure the parameters in the following way:

The 1734-IB4 is "Peer#0". Enter its produced data size, "1" as its input data
size. If the module does not consume data from this peer in four times the
expected packet rate (EPR), which is 400 ms in this case, the Peer #0
connection fault bit will be set.

The contents of the data are mapped to the Peer#0 data table.

To use the data from the 1734-IB4 in the DeviceLogix editor, click

to

place a Boolean bit input on the function block sheet, and select the desired bit
to use in logic under the "Network Boolean Input" category.

Parameter
number

Parameter
name

Parameter description

Default value

31

Peer#0 MacID

Slot number

No connection

39

Peer#0 Size

Input data size

24 bytes

65

Peer#0 EPR

Time out value

1000 ms

Parameter
number

Parameter
name

Parameter description

Value

31

Peer#0 MacID

Slot number

1

39

Peer#0 Size

Input data size

1 byte

65

Peer#0 EPR

Expected packet rate

100 ms