Publication 1734-UM015A-EN-E - November 2009

Troubleshooting 87

Network Status

DeviceLogix Status

I/O Status

Indication

Description

Recommended action

Off

Device is not online:
- Device has not completed
dup_MAC-id test.
- Device not powered – check
module status indicator.

Apply power to device, wait for
MAC_id to complete, and correct,
as needed.

Green

Device is online and has one or more
I/O connections in established state.

None.

Flashing
green

Device is online but has no
connections in established state.

None.

Flashing red

One or more I/O connections are in
the timed-out state.

Check for I/O module failure, and
correct, as needed.

Red

Critical link failure – failed
communication device. Device
detected error that prevents it from
communicating on the network.

Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.

Flashing
red/green

Device is in self-test.

None.

Indication

Description

Recommended action

Off

DeviceLogix program is not
controlling outputs.

None.

Green

DeviceLogix program is controlling
outputs.

None.

Flashing
green

At least one input in DeviceLogix
program is forced on/off.

None.

Indication

Description

Recommended action

Off

I/O is inactive.

None.

Yellow

I/O is active and under control.

None.