Status indicators of point i/o module, 1734-8cfgdlx module, Module status – Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 86

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

84 Troubleshooting

Status Indicators of POINT
I/O Module

See the figure and tables that show how to interpret the status indicators.

1734-8CFGDLX Module

Module Status

Indication

Probable Cause

Recommended Action

Off

No power applied to device.

Apply power to device.

Green

Device operating normally.

None.

Flashing
green

Device needs commissioning due to
missing, incomplete or incorrect
configuration.

Configure device properly.

Flashing red

Recoverable fault.

1. Cycle power to device.
2. If condition persists, replace
device.

Red

Unrecoverable fault may require
device replacement.

Replace device.

Flashing
red/green

Device is in self-test.

None.