Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 87

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

Troubleshooting 85

Network Status

DeviceLogix Status

I/O Status

Indication

Probable Cause

Recommended Action

Off

Device is not online.
- Device has not completed
dup_MAC_id test.
- Device not powered - check module
status indicator.

Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.

Green

Device is online and has connections
in the established state.

None.

Flashing
green

Device is online but has no
connections in the established state.

None .

Flashing red

One or more I/O connections are in
the timed-out state.
This could also mean a peer is not
producing data at all, or it is not
configured correctly.

Check I/O connection with
master. Verify peers are present
and configured properly.

Red

Critical link failure - failed
communication device. Device
detected error that prevents it
communicating on the network.

Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.

Flashing
red/green

Device is in self-test.

None.

Indication

Probable Cause

Recommended Action

Off

DeviceLogix program is not
controlling outputs.

None.

Green

DeviceLogix program is controlling
outputs.

None.

Flashing
green

At least one input in DeviceLogix
program is forced on/off.

None.

Indication

Probable Cause

Recommended Action

Off

Input or output is in the OFF state.

None.

Yellow

Input or output is in the ON state.

None.