Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 84

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

82 DeviceLogix Capabilities

To configure the message, do the following:

1. Click the ellipsis (…) button.

The Message Configuration dialog box appears.

2. Set the message type to “CIP Generic.”

3. Set the Service Type to “Set Attribute Single” to set data or “Get

Attribute Single” to read data.

4. Enter the Class value in hexadecimal from the table (“30A” is the Timer

function block).

5. Copy the Instance number from the upper left corner of the Timer

function block to which you are sending the message.

6. Enter the Attribute number in hexadecimal (“4” is the Preset Time).

7. Verify that the Source Element and Source Length (in bytes) is correct.

8. Click the Communication tab.

9. If you are using EtherNet/IP or ControlNet, click Browse to navigate to

the DeviceLogix module.

If you are using DeviceNet, browse to the DeviceNet Scanner
(1756-DNB) and enter Port "2" (for the DeviceNet port) and the node
number of the DeviceLogix module (node "4" in the following example)
separated by commas.

DeviceNet scanner name, port, node address