Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 47

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet 45

4. Enter the slot number in the Slot box.

It is not possible to make a Rack connection to the Point I/O
DeviceLogix module. The connection must be a direct one.

On the Connection tab, you can change the Requested Packet Interval
(RPI), the default is 20 ms.

The Module Info tab will display the status and identity information of
the module when the module is online.

There is no tab for configuration. Configuration of the Point I/O
DeviceLogix modules is done only using RSNetworx for DeviceNet.
See

Chapter 6

for more details.

RSLogix 5000 will create the following input tags:

AdapterName:SlotNumber:I.Data

AdapterName:SlotNumber:I.LogicDefinedData

AdapterName:SlotNumber:I.Status.LogicEnabled

AdapterName:SlotNumber:I.Status.Owned

AdapterName:SlotNumber:I.PeerMissing

AdapterName:SlotNumber:I.LogicDefinedIntData[0...7]

RSLogix 5000 will create the following output tags:

AdapterName:SlotNumber:O.Data

AdapterName:SlotNumber:O.LogicDefinedData

AdapterName:SlotNumber:O.LogicDefinedIntData[0...7]