Stand alone devicelogix, Peer enabled point i/o, Stand alone devicelogix peer enabled point i/o – Rockwell Automation 1734-XXXX POINT I/O and ArmorPOINT I/O DeviceLogix User Manual User Manual

Page 13

Advertising
background image

Publication 1734-UM015A-EN-E - November 2009

Introduction 11

Stand Alone DeviceLogix

If DeviceLogix is enabled (programmed), then the module becomes the owner
of its outputs. The DeviceLogix program reads inputs and controls the
onboard outputs.

The produced assembly may be shared with a controller if a connection
exists.

As the owner of its local outputs, the module may run without an
external controller.

An external controller, which is the owner of the connection to the module,
can influence the module’s logic via a consume assembly – both digital and
analog data. Configuration of the module is performed via RSNetWorx for
DeviceNet. When used on ControlNet or EtherNet/IP, the tool bridges
through the adapter to directly communicate with the DeviceLogix module on
the POINT I/O backplane.

Peer Enabled POINT I/O

The POINT I/O DeviceLogix module can “listen in” on data connections to
other POINT I/O modules on the backplane. This data can be used in the
DeviceLogix program to control the outputs. It can consume data from 8
different peers. The data from each peer can be up to 24 bytes long. The data
can be digital, analog (16-bit), or a mixture. The module supports the “Auto
Produce” parameter to produce I/O data automatically without the need for a
master. It will also produce and consume network data. Configuration of peer
data is performed via RSNetWorx.

See

Chapter 6, Configuring POINT I/O and ArmorPOINT I/O DeviceLogix

modules using RSNetworx for DeviceNet

.

Advertising