Troubleshooting, Zones, valves and bicoders, Soil moisture bisensors – Baseline Systems BaseStation 3200 User Manual

Page 53: 4troubleshooting

Advertising
background image

C h a p t e r 4 – T r o u b l e s h o o t i n g

Page 51

Baseline 3200

4

Troubleshooting

Section Contents

Zones, Valves and biCoders ................................................................................................51

Soil Moisture biSensors ......................................................................................................51

Two-Wire – High Current or Shorted ..................................................................................52

Lost Devices | No Response ................................................................................................53

Messages | Alerts ...............................................................................................................53

Zones, Valves and biCoders

The following table identifies some common problems and solutions. For all of these types of
problems, start with a zone self-test.

1.

Turn dial to Self-test position.

2.

Highlight the Test Zone menu and press ENTR.

3.

Use the + and – keys to select the zone number.

4.

Press ENTR to test the zone (this will activate the valve for less than a second to
measure the voltage and current through the valve solenoid). This test will return the
solenoid current and the

Self-test status

Cause/Action

Open circuit

Wire connection between the valve biCoder and the valve
solenoid is broken – repair wire connections.

Valve solenoid is broken – replace solenoid.

Short circuit

Wire connection between the valve biCoder and the valve
solenoid is shorted together – repair wire connections.

Valve solenoid is broken – replace solenoid.

No response

Two-wire connection to the valve biCoder is broken – repair
wire and connections to the valve biCoder.

Two-wire voltage loss is too high – check other devices in
same vicinity for high two-wire voltage loss – repair high
resistance connections between controller and devices.

Valve biCoder is damaged – remove biCoder and move it
directly to the controller to test its ability to communicate.

Soil Moisture biSensors

The following table identifies some common problems and solutions. For all of these types of
problems, start with a biSensor self-test.

1.

Turn dial to Self-test position.

2.

Highlight the Test biSensor menu and press ENTR.

3.

Use the + and – keys to select the biSensor number.

Advertising