558

Fabric OS Message Reference

53-1002749-01

HIL-1502

5

HIL-1502

Message

Slot <slot number>, high temperature (<measured temperature>). Unit will be shut
down in 2 minutes if temperature remains high.

Message Type

FFDC | LOG

Severity

CRITICAL

Probable Cause

Indicates that the temperature of this blade has risen above the critical threshold. This usually follows a
high-temperature message.

Recommended

Action

Run the fanShow command to verify all the fans are working properly.

Make sure that the area is well-ventilated and that the room temperature is within operational range of
your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.

If the message persists, replace the blade.

HIL-1503

Message

Slot <slot number>, unit shutting down.

Message Type

FFDC | LOG

Severity

CRITICAL

Probable Cause

Indicates that the temperature of this blade has been above the maximum threshold for at least two
minutes. The blade is shut down to prevent damage. This usually follows a high-temperature warning
message.

Recommended

Action

Run the fanShow command to verify all the fans are working properly.

Make sure that the area is well-ventilated and that the room temperature is within the operational range
of your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.

If the message persists, replace the faulty blade.

HIL-1504

Message

System within normal temperature specifications (<measured temperature> C).

Message Type

LOG

Severity

INFO

Probable Cause

Indicates that temperatures in the system have returned to normal.

Recommended

Action

No action is required.