Table 10-4. SERIAL Port Serial Commands

Command

Description

Values

EDP.PORT

Active serial port

Returns number of port being used for serial command input

EDP.INPUT#p

Port serial input function

CMD, KEYBD, SCALE, IND SC

EDP.BAUD#p

Port baud rate

300, 600, 1200, 2400, 4800, 9600, 19200, 28800, 38400, 57600,
115200

EDP.BITS#p

Port data bits/parity

8NONE, 7EVEN, 7ODD, 8ODD, 8EVEN

EDP.TERMIN#p

Port termination character

CR/LF, CR

EDP.STOPBITS#p

Port stop bits

2, 1

EDP.ECHO#p

Port echo

ON, OFF

EDP.RESPONSE#p

Port response

ON, OFF

EDP.EOLDLY#p

Port end-of-line delay

0–255 (.01-second intervals)

EDP.HANDSHK#p

Port handshaking

OFF, XONXOFF, HRDWAR

EDP.PORTTYPE#p

Port type

232, 485 (Port 7 only)

EDP.DUPLEX#p

Port RS-485 duplex

HALF, FULL

EDP.ADDRESS#p

Port RS-485 address

0, 1–255

EDP.STREAM#p

Port streaming

OFF, LFT, INDUST, 4KEYS, KEYPAD

EDP.SOURCE#p

Port source scale for output

scale_number

EDP.SFMT#p

Port custom stream format

0-50 characters

STR.POS#p

Custom stream identifiers

Specify replacement text for token

Example: STR.PRI#1=L

See Section 11.6 on page 106 for more information about custom
stream formatting.

STR.NEG#p

STR.PRI#p

STR.SEC#p

STR.TER#p

STR.GROSS#p

STR.NET#p

STR.TARE#p

STR.MOTION#p

STR.RANGE#p

STR.OK#p

STR.INVALID#p

STR.ZERO#p

For commands including “#p”, p is the serial port number.

Serial Commands

89

SC.WLIN.V1#1–
SC.WLIN.V5#1

Test weight value for linearization points
1–5

0.000001–9999999

SC.WLIN.C1#1–
SC.WLIN.C5#1

Calibrate linearization points 1–5

SC.LC.CD#1

Deadload coefficient

SC.LC.CW#1

Span coefficient

SC.LC.CZ#1

Temporary zero

SC.REZERO#1

Rezero

Command

Description

Values

Table 10-3. SCALES Serial Commands (Continued)