Ul-canada listed systems – Interlogix Concord Express Installation Manual User Manual

Page 11

Advertising
background image

Chapter 1

Concord Express Installation Instructions

5

• AC FAILURE set to on
• PHONE NUMBER must be programmed
• HIGH LEVEL REPORTS set to on.
• LOW LEVEL REPORTS set to on
• PHONE TEST set to on
• AUTO PHONE TEST set to on
• PHONE TEST FREQ. set to 1
• NEXT PHONE TEST set to 1
• LOW CPU BATTERY set to on
• COMM FAILURE set to on
• RF TX TIMEOUT set to 4 hours

Central Station Reporting

The panel has been tested with the following central station receivers using SIA
and Contact ID reporting formats:

• CS-5000 Central Station Receiver

• Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2

UL-Canada Listed Systems

This section describes the requirements for ULC (UL Canada) Listed systems.

• CSA Certified Accessories

The UL-Canada Basic System is nearly the same as the “UL Basic System”
described previously, the only difference being that you must use the ITI 60-
679-CN Class II transformer (Basler part number BE 116250-AAA) to power
the panel.

• Residential Burglary Alarm System Unit

(CAN/ULC-S309)
Same as “UL Basic System and Household Burglary Alarm System Unit (UL
1023)” described previously and siren timeout must be set to 5 minutes or
more.

Residential Fire Warning System Control Unit (CAN/ULC-S545-M89)

Same as “UL Basic System and Household Fire Warning System (UL 985)”
described previously.

Note

: For 24-hour backup, external power drain is limited to 90 mA continuous

using a 4.0AH battery.

California State Fire Marshall Listed Systems

Same as Household Fire Warning System (UL 985), plus: