Chapter 3

72

Concord Express Installation Instructions

Basic system commands

Table 4 below describes the basic system touchpad operating commands. For
complete details on system operation, including user programming, refer to the
system users guide.

Table 4: Basic system commands

Command

Response

* (STATUS)

Indicates current system status

1 + CODE

Disarms system to OFF

2 + CODE

Arms system to STAY

3 + CODE

Arms system to AWAY

2 (quick arm on)

Arms system to STAY

3 (quick arm on)

Arms system to AWAY

2 or 3 + CODE + 4
or
2 or 3 + 4

Makes entry/exit doors instant (4 must be pressed within five seconds
of arming)

5 + 2 or 3 + CODE
or
5 + 2 or 3

Arms system silently (no arming status beeps)

7 + 1

Turns chime feature on and off

7 + 6

Identifies alarms in memory

8 + CODE + 2

Initiates a phone test

8 + CODE + 3

Initiates a sensor test

8 + installer CODE + 3 Initiates a dealer sensor test

Testing Zones/Sensors

We recommend that you test sensors/zones after all programming is completed
and whenever a zone/sensor-related problem occurs.

If the system does not respond as described in the following procedure, see the
“Troubleshooting” section.

Note

: While the sensor test is a valuable installation and service tool, it only tests

sensor operation for the current conditions. You should perform a sensor test
after any change in environment, equipment, or programming.

1. Place all sensors/zones in their non-alarm state.

2. At an alphanumeric touchpad, enter the sensor test mode by pressing 8 +

installer CODE + 3. The touchpad sounds one beep and displays SENSOR
TEST, 15 MINUTES LEFT. The system stays in sensor test for 15 minutes.