Connecting Detection Devices to Panel Zone Inputs

The panel comes with six factory programmed onboard hardwire zones (see
“Accessory Modules Menu” on page 60 for factory settings). Zone inputs 1
through 6 are supervised using a 2k-ohm, end-of-line resistor (included with
panel) at the last device on the circuit.

Note

: Install an end-of-line resistor on all unused, factory programmed, onboard

panel zones.

All six zones accept either normally open (N/O) or normally closed (N/C)
detection devices (see Figure 8 on page 15).

The maximum loop resistance for each zone input is 300 ohms, plus the 2k end-
of-line (EOL) resistor.

Connecting Intrusion Detection Devices

Figure 8 on page 15 shows the typical wiring for N/C and N/O door/window
intrusion detection.