Chapter 3

Concord Express Installation Instructions

79

11. For pagers, extend the pager delay setting (see the PHONE OPTIONS—

GLOBAL

menu in the “Entering programming mode” on page 28.

Downloading/Uploading

Download/upload session fails on a pre-programmed panel.

1. Check all phone troubleshooting Action/Solution steps.

2. Verify Downloader Phone Number matches ToolBox setting.

3. Verify Downloader Code matches ToolBox setting.

4. Verify Dealer Code matches ToolBox setting.

5. Verify panel Account Number matches ToolBox setting.

Download/upload session fails on an unprogrammed panel.

• Check all phone troubleshooting Action/Solution steps.

Hardwire Zones

System doesn’t go into alarm when zone is tripped.

1. System is disarmed. Arm system and then trip the zone.

2. Zone is not learned into panel memory. Enter installer/dealer program mode

and use the LEARN SENSORS menu to add the zone into memory.

Zone reports trouble condition.

1. Check that onboard and SnapCard zone inputs have a 2k-ohm EOL resistor

installed at the last device on the loop (in series for N/C loops or in parallel for
N/O loops).

2. Check for zone wire fault—short circuit on N/C loops, open circuit on N/O

loops.

3. Make sure all devices on zone are in non-alarm state, then enter disarm

command to reset zone.

Panel Power

Panel does not power up. Touchpads don’t display or respond.

1. Check that panel transformer is plugged into an unswitched outlet.

2. Check the AC circuit breaker to be sure the circuit is live.

3. Check that the backup battery is installed correctly and the AC power

transformer is plugged in.

4. Check for proper panel and transformer wiring.