To Test Outputs:

1. Contact the central monitoring station to inform them that you are testing the

system.

2. Verify that all wiring at the panel and output devices is correct.

3. Activate the appropriate device to trigger each output as programmed.

4. Verify that each output responds according to the programmed configuration

number. For outputs that trigger sirens, verify that the correct alarm sounds
are produced from these sirens. Table 7 on page 76 describes the system
alarm sounds you should hear for each alarm event.

Contact the central monitoring station when you are finished testing.

Caution:

Be sure to contact the central monitoring station before activating

outputs that trigger from an alarm condition.

Table 5: Pager system event codes

Code

System event

009

Zone Restoral

111

System Disarmed

118

Trouble Condition Cleared

119

Alarm Canceled

222

System Armed to STAY

333

System Armed to AWAY

555

Phone Test

888

System Trouble Condition

999

System in Alarm

Table 6: Pager codes

Code

System event

000

System event not caused by a zone or user

001 - 0024 Sensor/Zone Numbers 1 - 24

600 - 615

Regular User Codes 0 - 15 used

678

System Master Code used

679

Installer Code used

680

Dealer Code used

697

Quick Arm used

698

Keyswitch Sensor used