NAV440 User Manual

7430‐0131‐01 Rev. F 

 

 

 

The first phase of operation is the high‐gain initialization phase.  During the initialization phase, the unit is expected 

to be stationary or quasi‐static so the EKF weights the accelerometer gravity reference and Earth’s magnetic field 
reference heavily in order to rapidly estimate the X, Y, and Z rate sensor bias, and the initial attitude and heading of 

the unit.    The initialization phase lasts approximately 60 seconds, and the initialization phase can be monitored in 

the software Status BIT transmitted by default in each measurement packet.    After the initialization phase, the unit 
operates with lower levels of feedback (also referred to as EKF gain) from the accelerometers and magnetometers to 

continuously estimate and correct for roll, pitch, and heading (yaw) errors, as well as to estimate X, Y, and Z rate 
sensor bias. 
The AHRS440provides the same scaled sensor and angle mode packets of the VG440. The AHRS440 defaults to the 
A1 Angle Packet which outputs the roll angle, pitch angle, yaw angle, and digital IMU440data.   In the AHRS440, the 
A0

 and A1 packets contain accurate magnetometer readings.   Refer to Chapter 9. Communicating with the 440 and 

Chapter 10. Programming Guidelines for full packet descriptions. 

NOTE: For proper operation, the unit relies on magnetic field readings from its internal 3‐axis magnetometer.    The 

unit must be installed correctly and calibrated for hard‐iron and soft iron effects to avoid any system 

performance degradation. Refer to Chapter 4. Magnetometer Calibration and Alignment Guidelines for 

information about magnetic calibration; review that information before using the AHRS440. 

NOTE:  The unit must be mounted at least 24” away from large ferrous objects and fluctuating magnetic fields.  

Failure to locate the unit in a clean magnetic environment will affect the attitude solution. 

AHRS440 Advanced Settings 

In addition to the configurable baud rate, packet rate, axis orientation, and sensor low‐pass filter settings, the unit 
provides additional advanced settings which are selectable for tailoring the unit  to specific application 

requirements.  The AHRS440 advanced settings are listed in 

  below: 

Table 7

Table 7AHRS 440 Series Advanced Settings 

Setting 

Default Value 

Comments 

Baud Rate 

38400  

9600, 19200, 57600 also available 

Packet Type 

A1 

S0, S1, S2, A0, A2, N0, N1 also available 

Packet Rate 

25 Hz 

This setting sets the rate at which selected Packet Type, packets are output.  If 
polled mode is desired, then select Quiet.   

Orientation 

See Figure 4 o
page 22. 

To configure the axis orientation, select the desired measurement for each axis: 
NAV‐VIEW 2.2 will show the corresponding image of the unit, so it easy to 

visualize the mode of operation.  Refer to Orientation Field on page 84 for the 

twenty four possible orientation settings.  The default setting points the 
connector AFT. 