10-19

evtWarmup OFF

To define exit conditions, follow these steps:

1. Drag a Condition Definitions shape from the LonPoint Scheduler stencil to

your LonMaker drawing.

2. Double-click the Condition Definitions shape. A drawing of the shape opens

in a new window.

3. For each exit condition definition, click an entry in the Exit Condition

column and type an Exit Condition name. Then click an entry in the
Definition column and type an Exit Condition expression. Close the Exit
Condition shape drawing window.

Following is an example Condition Definitions shape. This shape defines the
exit conditions for the example described in Drawing a State Machine Bubble
Diagram
earlier in this chapter.

cndSystemOn

cndSystemOff

cndOccupied

cndUnoccupied

cndStartWarmup

cndEndWarmup

cndEmergency

cndCancelEmergency

iSystemEnable On

iSystemEnable Off

(iOccupiedOverride On) OR (Powerloss On)

(evtOccupied Off) AND (iOccupiedOverride Off)
AND (evtWarmup Off)

evtWarmup On

(evtWarmup Off) OR (iReturnAirTemperature > 16)
OR (Powerloss On)

iEmergency On

(iOccupiedOverride On) OR (Powerloss On)

Exit Condition

Exit Condition Definitions

1. Use an additional Exit Condition Definitions shape for additional definitions.