5-4

Digital Encoder Functional Block

Lookup Tables

This tab appears as follows:

This tab contains the lookup table that determines the output of the
Digital_Out

and Mode_Out network variables based on the values of the 4

digital inputs. Each row of the table corresponds to one of the 16 possible
combinations of input values from the four digital inputs.

For each combination of inputs, you can set an output value for the
Digital_Out

network variable in the Digital Output column and the

Mode_Out

network variable in the Mode Output column. The fields in the

Digital Output

column can be set to 0 to send an Off digital state, 200 to send

an On digital state, or a value between 0 and 200 to send an On value with a
level less than 100% (the level is one half the specified value).

The available values in the Mode Output column depend on the type of the
Mode_Out

network variable selected on the Digital Encoder tab.